NBS National BIM Library

Rada Sense - Shower T3

Rada Sense - Shower T3

Rada - Kohler Mira Ltd
Cromwell Road
Cheltenham
Gloucestershire
GL52 5EP

Tel +44 (0)844 571 1777

Need specialist advice?
Get technical help
 

Rada Sense - Shower T3

Concealed digital mixing valve for shower, offering non-touch flow and temperature control, programmable maximum, minimum and default temperatures, duty flush and thermal disinfection with data logging capabilities.

  • ƒBuildcert TMV3 Scheme Approved
  • ƒƒWRAS Approved
  • ƒƒRemotely located valve (up to 3m)
  • ƒNo-touch ON/OFF and temperature control
  • ƒƒProgrammable flow times and temperatures
  • ƒƒProgrammable ‘duty flushing’
  • ƒƒThermal disinfection with datalogging
  • ƒƒValve information and usage data
  • ƒƒIncorporating T-logic™ digital intelligence
Platform Compatible Version Certified to
AECOsim AECOsim - 1.0 -
IFC IFC 2X3 2 1.2
Revit Revit 2013 + 2 1.2

Download

Rada - Kohler Mira Ltd
Cromwell Road
Cheltenham
Gloucestershire
GL52 5EP

Tel +44 (0)844 571 1777

Need specialist advice?
Get technical help
 
  • Properties and values
  • More BIM objects

Properties and values

COBie
NBS_General
NBS_Data
Certification
Buildcert TMV3 Scheme Approved, WRAS Approved, BEAB approved
ColdWaterTemperatureRange
1-20°C
ControlPanelCableLength
3 m supplied (6 m maximum)
ControlPanelSize
234 x 26 x 120 mm
DigitalMixingValveSize
511 x 86 x 188 mm
FactoryPresetDisinfection
Minimum 5 min at 60°C
FactoryPresetDutyFlushCycle
2 min
FactoryPresetDutyFlushWaitingPeriod
12 h
FactoryPresetFlowTime
30 s
FactoryPresetTemperatureRange
Minimum 30°C, maximum 41°C, default 38°C
FittingSize
n/a
HotWaterTemperatureRange
60-65°C (85°C during disinfection)
IntegralAccessories
Pocket PC (PDA)
MaximumHumidity
95% non-condensing
MaximumStaticPressure
10 bar
MaximumWaterSupplyTemperature
41°C
MinimumBlendTemperatureDifferential
2°C
MinimumFlowRate
6 L/min at <5 bar, 8 L/min at >5 bar
MinimumPressureLoss
0.2 bar
OperatingTemperature
1-40°C
OptimumThermostaticControlRange
30-50°C
ProgrammableDisinfection
Minimum 0-50 min at 60-85°C
ProgrammableDutyFlushCycle
1-59 min
ProgrammableDutyFlushWaitingPeriod
1-983 h
ProgrammableFlowTime
5 s - 60 min
ProgrammableTemperatureRange
Minimum 30-47°C, maximum 33-50°C, default 30-50°C
TemperatureStability
U+00B11°C
Pset_ElectricalDeviceCommon
Pset_FlowMeterTypeCommon
Pset_FlowMeterTypeWaterMeter
Pset_ValveTypeCommon
Pset_ValveTypeFaucet