NBS National BIM Library

Rada Sense - Bidet Kit T3

Rada Sense - Bidet Kit T3

Rada - Kohler Mira Ltd
Cromwell Road
Cheltenham
Gloucestershire
GL52 5EP

Tel +44 (0)844 571 1777

Need specialist advice?
Get technical help
 

Rada Sense - Bidet Kit T3

Concealed digital mixing valve for bidet, offering programmable maximum, minimum and default temperatures, duty flush and thermal disinfection with data-logging capabilities.
Supplied complete with programmable software, power supply, check valves and strainers. Wall mounted control panel offering infra-red no-touch controls for flow and temperature adjustment and programmable timed flow control.

With deck mounted bidet spout for ‘over the rim’ delivery supplied with 5 l/min flow regulator.

  • ƒBuildcert TMV3 Scheme Approved.
  • ƒƒWRAS Approved.
  • ƒƒRemotely located valve (up to 3 m).
  • ƒƒThe world’s first digital mixing valve for commercial use.
  • ƒƒSets new standards of hygiene.
  • ƒƒNo-touch ON/OFF and temperature control.
  • ƒƒProgrammable flow times and temperatures.
  • ƒƒProgrammable ‘duty flushing’.
  • ƒƒSecure thermal disinfection with data-logging.
  • ƒƒValve information and usage data.
  • ƒƒIncorporating T-logic™ digital intelligence.
Platform Compatible Version Certified to
AECOsim AECOsim - 1.0 -
IFC IFC 2X3 2 1.2
Revit Revit 2013 + 2 1.2

Download

Rada - Kohler Mira Ltd
Cromwell Road
Cheltenham
Gloucestershire
GL52 5EP

Tel +44 (0)844 571 1777

Need specialist advice?
Get technical help
 
  • Properties and values
  • More BIM objects

Properties and values

COBie
NBS_General
NBS_Data
Certification
Buildcert TMV3 Scheme Approved, WRAS Approved, BEAB approved
ColdWaterTemperatureRange
1-20°C
ControlPanelCableLength
3 m supplied (6 m max)
ControlPanelSize
234 x 120 x 26 mm
DigitalMixingValveSize
511 x 188 x 86 mm
FactoryPresetDisinfection
Minimum 5 min at 60°C
FactoryPresetDutyFlushCycle
2 min
FactoryPresetDutyFlushWaitingPeriod
12 h
FactoryPresetFlowTime
15 s
FactoryPresetTemperatureRange
Minimum 30°C, maximum 38°C, default 36°C
HotWaterTemperatureRange
50-65°C (85°C during disinfection)
IntegralAccessories
Pocket PC (PDA)
MaximumHumidity
95%
MaximumStaticPressure
10 bar
MaximumWaterSupplyTemperature
41°C
MinimumBlendTemperatureDifferential
2°C
MinimumFlowRate
4 L/min at <5 bar, 6 L/min at >5 bar
MinimumPressureLoss
0.2 bar
OperatingTemperature
1-40°C
OptimumThermostaticControlRange
30-50°C
ProgrammableDisinfection
Minimum 0-5 minutes at 60-85°C
ProgrammableDutyFlushCycle
1-59 min
ProgrammableDutyFlushWaitingPeriod
1-983 h
ProgrammableFlowTime
5 s - 60 min
ProgrammableTemperatureRange
Minimum 30-47°C, maximum 33-50°C, default 30-50°C
TemperatureStability
U+00B11°C
Weight
We
Pset_ElectricalDeviceCommon
Pset_FlowMeterTypeCommon
Pset_FlowMeterTypeWaterMeter
Pset_ValveTypeCommon
Pset_ValveTypeFaucet
Pset_ValveTypeMixing

More BIM objects

Terms and conditions

Please agree to the updated terms and conditions

Thank you, your registration was complete
Thank you
Your query has been sent.

A technical consultant from will be in touch soon.
Manufacturers using NBS National BIM Library adhere to our code of conduct.