Energimizer 50 NG- Packaged combined heat and power (CHP) units

Select regional version:

Download

The object content is configured for use in UK, but it may also be suitable for use in other locations.

Tags:

The Energimizer CHP range deliver highly efficient Combined Heat & Power with industry leading low NOx emissions and quiet running compact sized modules.

Designed and manufactured in Germany by KW Helec have several hundred running CHP’s located throughout sites in the UK.

Helec also provide plant room design support and are happy to assist with securing specification, supply and commission along with ongoing service requirements.


5 sizes are available in this range from 7.5kWe, 16kWe, 22kWe, 33kWe & 50kWe.

Platform Compatible Version Certified to
IFC IFC - 1 1.3
Revit Revit 2016 + 2 2.0

  • Properties and values
  • More BIM objects
  • What's Changed?

Properties and values

COBie
NBS_General
NBS_Data
AmbientTemperature
5˚C to maximum 35˚C
CarbonMonoxide
< 35="" mg/m³="" (50%="">
CHPCoefficient
0.57
CombustionAirRequirement
minimum 600 m³/h
ElectricalGeneratorStandard
n/a
ElectricalGeneratorType
n/a
ElectricEfficiency
36.0% (net) 32.4% (gross)
EnergyEfficiency
A++
ExhaustGasConnection
DN120
ExhaustGasEmissions
at 5% Volume remaining oxygen
FlowRateNaturalGas
14.7 Nm³/h
FlowTemperature
maximum 90°C
FuelConsumption
137 kW 1) (net) 150.7 kW (gross)
FuelOptions
Natural gas or LPG
GasConnection
R 1ȝ NG
GasConnectionPressure
20-50 mbar
GasFlowPressure
≤16 mbar
HeatingConnections
R 1¼201D Flow (warm) & R 1¼201D Return (cold)
IntegralMeteringEquipment
n/a
InterconnectionToBuildingManagementAndMonitoringSystemBMMS
n/a
MaximumSystemPressure
6 bar (heating side)
MonitoringDisplayTheFollowingConditionsElectricalProperties
n/a
MonitoringDisplayTheFollowingConditionsEnvironment
n/a
MonitoringDisplayTheFollowingConditionsHeatExchanger
n/a
MonitoringDisplayTheFollowingConditionsPrimeMover
n/a
MonitoringDisplayType
LCD
MonitoringMetering
n/a
MotorCylinder
4
MotorDisplacement
4.9 L
MotorOpertation
4-stroke
MotorType
Straight line
NitrogenOxide
< 26="" mg/m³="" (50%="">
OperationalMode
Mains parallel operation
OutputThermalPower
90.2 kW minimum 57.0 kW
PrimeMover
Internal combustion engine
ReturnTemperature
maximum 70°C
SoundPressureLevel
~ 55 dB(A) (1 m distance)
ThermalEfficiency
0.73
TotalEfficiency
109.4% (net) 99.45% (gross)
Pset_ElectricalDeviceCommon
Pset_TankTypeCommon

More BIM objects

What's Changed?