xvent (AOV) rooflight has been tested and certified to BS EN 12101-2:2003. On installation it is connected to the fire alarm system which if triggered will automatically open the unit to 140° for smoke ventilation. If connection to the fire alarm panel is lost it will automatically open and should the fire alarm system fail completely, the integrated thermostat will trigger the unit to fire position should the internal temperature reach 72°.

When running off the battery the xvent will emit an audible signal and the LED control switch will flash Red. The xvent has dual functionality and can also be used day to day as a vent unit opening up to 45°. Glazing Vision’s xvent is available in two standard sizes providing internal clear openings of either 1m² or 1.5m² and can even be integrated into the Flushglaze system for larger roof glazing requirements.

xvent can be supplied with a laminated inner pane which has been attack tested to LPS2081 Issue 1: 2015 and rated Secured by Design.

Platform Compatible Version Certified to
IFC IFC 2X3 1 1.3
Revit Revit 2016 + 2 2.0

  • Properties and values
  • More information
  • More BIM objects
  • What's Changed?

Properties and values

COBie
NBS_General
NBS_Data
Accessories
External clip on cover, Remote control, Rain sensor, Thermostat, BMS integration, Security system integration, RITEC coating,
AerodynamicFreeArea
0
Arrangement
Glazed
CavityType
20 mm black silicone sealed warm edge argon filled
Certification
CE Marked to BS EN 12101-2:2003, DOP No. 001GV2013-50-28
ComponentNumber
n/a
Controls
Dual scissor actuator drive, on board PCB housed within IP rated protective enclosure
DriveMechanism
Motor driven parallel linkage mechanism with encoder feedback
Guards
n/a
Initiation
Automatic device activated by a signal from the fire alarm with additional temperature redundancy at 72°
InnerPaneType
4 mm heat soak tested soft low e toughened
IntermediatePaneType
n/a
LowAmbientTemperatureClassification
T -15°C
MaterialsFinish
Principal components polyester powder coated
MaterialsFrame
Aluminium
MaterialsGlazing
30 mm insulating glass unit
MaterialsLouvers
n/a
MaximumArea
2.6 m²
MaximumSize
1900 mm width, 1400 mm span
MinimumSize
1400 mm width, 1400 mm span
OpeningAngle
104° AOV operation, 0-45° ventilation range
OpeningTime
≤60 seconds
OpeningType
Hinged for vent
OuterPaneType
6 mm heat soak tested toughened
PitchAngleRange
3-5°
PowerSupply
Extenal 28 V, 28 A, 750 W switch mode power supply; back up batteries included in case of mains failure
ReliabilityClassification
Re 50
ResistanceToHeatClassification
B 300°C
Seals
Combination of three silicone bubble seals
Security
Mechanism cannot be disconnected from lid whilst closed, mechanisms prevent the lid from being forced open
SnowLoadClassification
SL 125 Pa
ThermalBreak
true
WindLoadClassification
WL 1500 Pa
WindowNumber
n/a
Pset_DoorWindowGlazingType
Pset_ElectricalDeviceCommon
Pset_WindowCommon

More information

  • NBS specification data
  • More BIM objects

    What's Changed?

    7/10/2018

    Object upgraded to NBS BIM Object Standard v2.0.