DBiF501 Fabric Fire Curtain

Select regional version:

Download

The object content is configured for use in UK, but it may also be suitable for use in other locations.

Tags:

Fabric fire barrier designed to protect escape routes from the effects of fire, thus enabling building occupants to reach fire exits.  

Platform Compatible Version Certified to
IFC IFC - 1 2.1
Revit Revit - 1 2.1

  • Properties and values
  • More BIM objects

Properties and values

IFC
IfcExportAs
IfcDoorType
IfcExportType
DOOR
COBie
BOS_General
NBS_Data
Accessories
None, Photocell
Activation
Volt free electrical signal will trigger the door to close under power or gravity control/ part close/ close under smoke detection signal/ close when signalled by fire alarm/ close on timer/ show a visual display ' Shutter Closing'/ sound an audio warning/ trigger a controlled descent unit activated by a battery backup power system
Arrangement
Vertical roller shutter for face fixing
Barrel
Carbon steel tube finished with one coat rust inhibitive primer
BarrierUnits
n/a
ColourFinish
RAL 1021, RAL 3005, RAL 3020, RAL 5003, RAL 5005, RAL 5010, RAL 5013, RAL 5015, RAL 6005, RAL 6029, RAL 7016, RAL 7021, RAL 7031, RAL 7035, RAL 7037, RAL 8016, RAL 9001, RAL 9005 (BLACK), RAL 9006 (SILVER), RAL 9007, RAL 9010 (WHITE), RAL 9910, BS 00A05, BS 08B29, BS 04E53, BS 12B27, BS 18B25, BS 18E53, RAL 1015, Manufacturer's standard
ContainsRedListMaterials
n/a
CountryOfMaterialOrigin
n/a
CountryOfProductManufacture
n/a
Curtain
BS 1634-1 Fortress 240+ Fire Shield Fabric™ 640g/m² specially designed reinforced woven glass-fibre material coated on both sides with a reflective micronized aluminium polymer with an 120 min integrity and irradiance rating of 87 minutes. Galvanized steel bottom rail fabricated from 1.2 mm galvanized steel
Deployment
n/a
EmbodiedCarbon
n/a
EndPlates
2ȓ3m m (depending on curtain size/weight) carbon steel plates finished with one coat rust inhibitive primer
Execution
n/a
FrameMaterial
FortressSEFA_Steel
Grade
n/a
Guides
Fortress GCR-10 system™ 2/ 3 mm galvanized steel guides with a fabric retaining track system that prevents the curtain from dislodging from the guide under heat exhaust and ventilation pressure
Headbox
1.2 mm galvanized steel 175 x 175 mm box assembly (variable), houses the curtain operator, barrel and curtain assembly. BS EN 12453 Galvanized steel roll-formed base bar with Fortress Anti-Catch System™ designed to avoid any lifting hazard,
Operation
BS EN 12453 Fortress FC IBM™ single-phase operator supply with normal day to day operation by low voltage key switch (24 Volt) linked to the building fire alarm system. On receiving a signal from the fire alarm, the control panel will either close the curtain under power close or controlled decent gravity drop. Control panel must be connected to a 13 A/non switched fused spur located within 1 m of the motor position
PerformanceDurabilityClass
n/a
PerformanceFireResistance
120 minutes fire integrity and 87 minutes irradiance resistance BS 476-22, BS1634-1, 2 and BS EN 8524
PerformancePressureAndImpact
n/a
PerformanceReactionToFire
n/a
PerformanceSmokeContainment
Smoke performance BS EN 1634-3 <3 m³/h/m at 25Pa
Recyclability
n/a
RecycledContent
n/a
StandardsBarrierAssemblies
n/a
StandardsTestStandards
n/a
ThirdPartyCertification
n/a

More BIM objects