ADP65 – Air Pressure Switch (IP65)

Select regional version:

Download

The object content is configured for use in UK, but it may also be suitable for use in other locations.

Tags:

It is a requirement to prove that mechanical ventilation systems are operating in commercial catering establishments to comply with current British Standards. The ADP65 air pressure switch monitors positive, negative or differential air or flue gas pressure. Kit includes tubing and pitot connections.

Features and benefits:

  • Adjusting range: 20 – 330 Pa.
  • Maximum inlet pressure: 5000 Pa.
  • Switching hysteresis: 8 – 18 Pa.
  • Compliant with 73/23/EEC.
Platform Compatible Version Certified to
IFC IFC - 1 2.1
Revit Revit - 1 2.1

  • Properties and values
  • More BIM objects

Properties and values

IFC
IfcExportAs
IfcControllerType
IfcExportType
PROGRAMMABLE
COBie
BOS_General
NBS_Data
Accessories
n/a
Adjustability
The switching pressure can be adjusted using the hand setting dial and scale, the switching pressure has a tolerance of ± 15% from the set nominal value, adjusted in rising pressure and with a vertical diaphragm
AdjustingRange
20 - 330 Pa
Application
Pressure switch for air for monitoring positive, negative or differential air or flue gas pressure
MaximumInletPressure
5000 Pa
Operation
The ADP65 Air Pressure Switch works by switching over a relay contact when a difference in pressure is present, the pressure at which switching occurs can be set by altering a dial on the face of the ADP65
SwitchingHysteresis
8 - 18 Pa
Pset_ControllerTypeCommon
Pset_ControllerTypeProgrammable
Pset_ElectricalDeviceCommon

More BIM objects