Daikin Applied D-AHU Professional Hospital

Select regional version:

Download

The object content is configured for use in UK, but it may also be suitable for use in other locations.

Tags:

Daikin Applied AHU range covers air flow rates from 1,100 m3/h up to 124,000 m3/h with, the option to choose the most appropriate transverse velocity, depending on the treatment required.

AHU’s for medical facilities have high specification, ensuring units can be cleaned, maintained and failure resistant. Systems are designed for easy maintenance and access to each section enabling the unit and filters to be cleaned and the AHU’s have good visual inspection.

Internal component materials used will prevent legionnaire’s disease developing, such as, copper fin coils & stainless steel drip trays that do not ‘pool’.

Critical units will have either a run and standby fan/motor in case of failure; specialist theatres can have a complete standby unit.

Units are generally designed under positive pressure, so no contaminants from the plant area are drawn into the unit.

Eurovent certified & compliant with HTM03-01 (Health Technical Memorandum specialising in ventilation within health care premises).  

Platform Compatible Version Certified to
IFC IFC 2X3 1 1.3
Revit Revit 2016 + 4 2.0

  • Properties and values
  • More BIM objects
  • What's Changed?

Properties and values

COBie
NBS_General
NBS_Data
AccessOptions
Access doors, double-wall polycarbonate portholes
Accessories
n/a
AccessoryOptions
Range of spigots and flexible connections, louvres, control accessories, etc
AntivibrationMountings
Spring anti vibration mounts, tensioning slide and flexible connections
Certification
Eurovent
ComponentsAttenuators
Rectangular silencers as per client specification
ComponentsCoolingCoils
Warter and DX if required
ComponentsDampersMixing
Aluminium, galvanized and stainless steel as per client specification
ComponentsDampersShutOff
Aluminium, galvanized and stainless steel as per client specification
ComponentsFans
Centrifugal, direct drive, external drive, EC as per client request
ComponentsFilters
As per client specification
ComponentsHeatRecovery
Thermal wheel, plate heat exchanger, RAR coil, 3 way mixing dampers,and horse shoe heat pipe as per client specification
ComponentsHumidifiers
Evaporative, direct steam, atomizing and adiabatic as per client specification
ComponentsPreheaters
Electric, low temperature hot water, direct/indirect gas heater and DX as per client specification
ComponentsReheaters
Electric, low temperature hot water, direct/indirect gas heater and DX as per client specification
Construction
Double skin
ControlOptions
Optional sensors to regulate temperature, humidity,air quality, inverted drives, regulation valves, damper actuators, safety and control devices
DirectionOfAirflow
Horizontal
DutyAirVolume
n/a
DutyDischargeVelocity
n/a
DutyExternalResistance
n/a
DutySoundPowerLevel
n/a
Environment
External or internal
FanOptions
Forward bladed fan, backward bladed fan, plug fan
FilterOptions
Pleated, flat, rigid bag, soft bag, high efficiency, active carbon absorption, active carbon deodorizing
FlexibleConnections
Optional flexible connections
HeatRecoveryOptions
Heat wheel (sensible or enthalpy type), cross-flow, run-around coils
HumidificationOptions
Surface evaporation, water spray, steam,atomized
MethodOfSupport
Formed channel support
PanelInsulationOptions
Polyurethane or mineral wool
PositionsForMaintenanceAccess
Access doors
RecommendedAirVelocity
2.5 m/s for units including cooling coils
SizeOptions
Range of 27 fixed sizes, as well as custom sizes through increments of 50 mm
SpecificFanPowerVerification
n/a
ThermalEfficiencyWinter
n/a
Weight
n/a
Pset_DoorWindowGlazingType
Pset_ElectricalDeviceCommon