MxPro 4 Fire Alarm Control Panel 1 Loop

Select regional version:

Download

The object content is configured for use in UK, but it may also be suitable for use in other locations.

Tags:

The MxPro 4 comes fitted complete with an internal loop driver card (Apollo/Hochiki only) and 2 onboard sounder circuits. The control panel consists of a simple to use LCD menu driven graphical interface, dual, flash-based microprocessor technology driven by an onboard 24V DC, 2 Amp high efficiency switched mode power supply and charger approved to EN54 parts 2 & 4.

Dedicated system navigation keys make this control panel user-friendly as well as installer friendly due to the uncomplicated, trouble-free, commissioning and fault finding.

Powerful cause and effect programming coupled with dynamic zoning makes the panel suitable for a wide range of site applications, from small to large complex multi-area systems. Fully on-site programmable via on board alphanumeric
keypad or PC-NeT configuration tools.

An extensive suite of PC based, software programs have been developed to supplement the MxPro 4 series fire panels.

Features:

  • Full support of Apollo (Discovery, Xplorer S90 & XP95), Hochiki ESP protocols.
  • Advanced graphical LCD user interface with up to 250 fire zones as standard, allowing full EN54 compliance without additional hardware or LED indication.
  • Dedicated RS232 serial port for direct PC or modem connection.
  • Installer friendly auto-learn and loop detection facility for uncomplicated, trouble-free, commissioning and fault finding.
  • Fully on-site programmable via onboard alphanumeric keypad or PC configuration tools.
  • Flash memory and the advanced graphical display enables the panels to be configured to operate in virtually any language with any character set and allows the installer's logo and company details to be applied to the LCD display.
  • Robust, removable equipment chassis with plug-in connectors for simple fixing and cable termination.
  • When connected to the fault tolerant Ad-NeT network, the panel operates as a true peer-to-peer interface with full cross-panel reporting, control and cause-and-effect functionality.
Platform Compatible Version Certified to
IFC IFC - 2 2.0
Revit Revit 2017 + 2 2.0

  • Properties and values
  • More BIM objects
  • What's Changed?

Properties and values

IFC
IfcExportAs
IfcControllerType
IfcExportType
PROGRAMMABLE
COBie
BOS_General
NBS_Data
Controls
To BS EN 54-2
EnclosureMountingOptions
Surface, recessed
Indications
Fault signals from points
InputDevice
Via on-board keypad or pc running windows tools
InstalledCapacity
Single loop
MainDisplay
Backlit 240 x 64 graphical LCD
MonitoredSounderCircuitsMinimum
Two
Outputs
Output to fire alarm devices
Printer
Output to separate printer
StandbyPowerSupplyCapacity
24 V, 7 Ah internal , 24 V, 12 Ah external
StandbyPowerSupplyStandard
To BS EN 54-4
ZoneIndication
LCD user interface with up to 250 fire zones as standard, allowing full EN54 compliance without additional hardware or LED indication
Pset_ControllerTypeCommon
Pset_ControllerTypeProgrammable
Pset_ElectricalDeviceCommon